WCEP couldn't reach full output without exceeding the 140°F temperature limit of its buried HDPE cooling water header. Rather than default to an expensive rerating, McMillen built a calibrated thermo-hydraulic Datacor Fathom model and evaluated eight enhancement scenarios in isolation. The biggest culprit: fouling had cut heat exchanger effectiveness by approximately 60%.